| Test voltage |
From 500Vdc to 15kVdc
Adjustable in 500V steps |
| Preset buttons |
1kV, 5kV, 10kV, 15kV |
|
| Insulation resistance |
1000GΩ/0.5kV
1000GΩ at 0.5kV ~ 30TΩ at 15kV |
| Accuracy |
1kV: 0~200GΩ
5kV: 0~1TΩ
10kV: 0~2TΩ
15kV: 0~3TΩ |
±(5%rdg+5dgt) |
1kV: 200GΩ~2TΩ
5kV: 1TΩ~10TΩ
10kV: 2TΩ~20TΩ
15kV: 3TΩ~30TΩ |
±20% |
| Resolution |
1GΩ : 0.001GΩ
10GΩ : 0.01GΩ
100GΩ : 0.1GΩ
1000GΩ : 1GΩ
10TΩ : 10GΩ
30TΩ : 100GΩ |
| Short circuit current |
up to 5mA |
| PI (Polarization Index) |
V |
| DAR (Dielectric Absorption Ratio) |
V |
| Voltmeter |
ACV : 30~600V (50/60Hz)
DCV : 30~600V
Accuracy : ±(2.0%rdg+3dgt)
Resolution : 1V |
| Current measurement |
0.5nA ~ 0.55mA
(Depending on the insulation resistance) |
| Power source |
Rechargeable battery |
| Adapter |
Input : 100-240Vac, 0.4A, 50-60Hz
Output : 24Vdc, 0.62A |
| Dimensions |
430(L) x 324(W) x 127(D)mm |
| Weight |
Approx : 6.56kg |